Setting the PROFINET Station Name

To operate the PROFINET fieldbus coupler in a network, it must be assigned a
unique name.
This should be carried out via the DCP with the DIP switch or with a
configuration tool such as Step7 when the fieldbus coupler is connected to the
ETHERNET network and is ready for operation (BF LED flashed red). A station
name communicated via the DCP overwrites the current name and is saved
permanently.
The retentive memory for the station name is a DCP option.
A temporary name set via DCP deletes any name saved in retentive memory.
Restarting the device clears the name. In this case, the device has no name after a
restart (if DIP 9=Off).
If the option for retentive memory in DCP is set, the name is again available even
after restarting the device.
Switch 9 must be switched off for the fieldbus coupler to load the station name
from memory at each system start.
If assignment of the station name is desired via the DIP switch, then switch on
switch 9 when disconnected from power. The station name is selected via switch
8, and the instance is established using switches 1 through 7 (e.g.
wagox767x1201x1, wagox767x1201x2, ...). In the default status, the station
name is "wago-767-1201" (default setting).

Table 26: Default settings of DIP switch

Switch
Binary values 2
Switch setting Off Off Off Off Off Off Off Off
Requirement:
The fieldbus coupler is not connected to the power supply.
To set the station name via the DIP switch, proceed as follows:
1.
Open the cover by unscrewing the M3 screw with a screwdriver.
2.
Set the station name of the fieldbus coupler by switching on switch 9. Select
the station name with switch 8 (Off = wago-767-1201,
On = wagox767x1201).
3.
Use switches 1 through 7 to assign an instance to the fieldbus coupler.
4.
Close the cover and screw it securely in place to maintain degree of
protection IP 67.
Manual
Version 2.2.0
1
2
3
4
5
0
1
2
3
2
2
2
2
(1)
(2)
(4)
(8)
(16)
6
7
8
9
4
5
6
2
2
DN
DNI
(32)
(64)
Off
Commissioning
65
10
11
12
-
Boot/
Reset
Execute
Off
Off