Snmp V3" View; Table 32: Parameter Description Of The Page "Snmp V3 - WAGO -SPEEDWAY 767 Manual

Profinet io fielbus coupler for wago-speedway 767
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
7.3.6

"SNMP V3" View

The SNMP V3 network characteristics are configured on this page.
1.
To confirm your entries, click [SUBMIT].
To clear your entries, click [RESET].
2.
3.
Your entries are not active until the software has been reset. To reset the
software, click on "Administration" in the navigation bar and then
[Software Reset].
Alternatively, reset the software be cycling the system power supply.

Table 32: Parameter description of the page "SNMP V3"

SNMP Configuration V3 (User)
Entry
1. User / 2. User
Security Protocol
Security Name
Security Key
Privacy Enable
Privacy Key
Notification/
Trap Enable
Notification
Receiver IP
Manual
Version 2.2.0
Value
Description
Example)
Activating user 1 or 2
activate
Deactivating user 1 or 2
None
None
MD5
None
SHA1
None
Enter the name, if the "Security Protocol" MD5 or SHA1
SecurityName-x
has been selected.
Enter the password with at least 8 characters, if "Security
Security Key
Protocol" MD5 or SHA1 has been selected.
Activate the DES encryption of the data
DES
Deactivate the DES encryption of the data
Enter the password of at least 8 characters in the
Privacy Key
encryption with DES
Activate the notification traps of the SNMP version 3
V3
Deactivate the notification traps of the SNMP
version 3
192.168.1.10
IP address of the notification manager
Commissioning
No encryption of the
MD5
SHA1
authentication
Encryption of the
MD5
SHA1
authentication with MD5
Encryption of the
MD5
SHA1
authentication with SHA1
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

767-1201