114
Acyclic Services
10.2
Parameter Services
The parameterization of the 767-1201 PROFINET coupler is only possible via the
acyclic services, for which the index 4000
After configuration of the fieldbus coupler, the IO Controller conveys the
parameterization data in order to change the settings of the coupler and the I/O
modules according to the configuration. An overview of the parameters that are to
be set can be found in section "Parameterizing".
The coupler and the I/O modules can also exchange data without parameterization
with an IO Controller. In this case, the settings used are the standard settings
designated in cursive in section "Parameterizing".
10.3
Diagnostic Services
The diagnostic services help to read out disruptions in the fieldbus coupler or the
I/O modules. The PROFINET specification defines various data sets in this
regard. The following table lists several diagnostic services:
Table 60: Diagnostic services
Index
0x800B
0x800C
0xC00B
0xC00C
0xE00B
0xE00C
0xF00B
0xF00C
The structure of the diagnostic data is the same for each data set in the
conveyance and is displayed in section "Diagnostics".
Pos : 43 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Access
Description
authorization
R
Diagnostic data of a sub-module
R
Diagnostic data, maintenance data and status data of a sub-
module
R
Diagnostic data of a module
R
Diagnostic data, maintenance data and status data of a
module
R
Diagnostic data of a communication relationship
R
Diagnostic data, maintenance data and status data of a
communication relationship
R
Diagnostic data for a defined profile (API)
R
Diagnostic data, maintenance data and status data for a
defined profile (API)
WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
is to be used.
H
Manual
Version 2.2.0