WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
•
For both power supply and S-BUS (system bus), use only pre-assembled
WAGO system cables. This is the only means whereby the specified
characteristics of the technical data can be achieved.
Pos : 25.7 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/Fel dbus koppl er/Ansc hluss_Hi nweise Teil 3 @ 7\mod_1268906367977_21.doc x @ 53450 @ @ 1
•
Keep all cables a sufficient distance away from electromagnetic sources of
interference in order to maintain a high level of interference resistance of
the 767 system against electromagnetic emissions.
•
Observe the minimum bending radiuses of the WAGO system cable. For
more information, see the technical data at www.wago.com.
•
When laying all cable, ensure that you do not lay it in shear areas of moving
machine parts.
•
The cable shield of the fieldbus cable must be connected with functional
ground on both ends over a wide area.
•
Observe the correct layout of the potential equalization.
Pos : 25.8 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/Fel dbus koppl er/Ansc hluss_Hi nweise Teil 3 (nic ht 767- 1401) @ 7\mod_1268909851033_21.doc x @ 53534 @ @ 1
•
Do not use drop lines under any circumstances. This can lead to amplified
line reflections and signal distortions, which greatly impair the transmission
quality.
Pos : 25.9 /Serie 767 (WAGO-SPEED WAY)/Ans chl uss D aten- und Vers orgungs kabel/Fel dbus koppl er/Ansc hluss_Z ubehör @ 7\mod_1268906370477_21.doc x @ 53470 @ 2 @ 1
6.2
Required Accessories
The WAGO accessories listed below are required for connecting the data and
supply cable. The associated item numbers can be found in the "Accessories"
section.
•
S-BUS M12 terminator, IP 67
•
S-BUS and supply cables, pre-assembled on both ends, IP 67
•
USB cable pre-assembled on both ends, IP 67
Pos : 25.10 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 2.2.0
Connecting Data and Supply Cables
51