60
Connecting Data and Supply Cables
Pos : 25.22 /Serie 767 ( WAGO-SPEED WAY)/Ansc hluss D aten- und Versorgungs kabel/I/O-M odule/Ansc hlus s_Sens oren 767- 1xxx, -2xxx, - 38xx_8xM 8 @ 5\mod_1249292506750_21.doc x @ 39918 @ 2 @ 1
6.6

Connecting the Sensor Cables

The sensor cables provide power to the connected sensors and transmit the sensor
signals.
When using cables that have not been pre-assembled, make sure that these cables
are equipped with M8 plugs rated to IP 67. The following table outlines the
assignment of the sensor connections:

Table 24: Connection assignment of digital inputs

Connection
IN
X1, X3, X5, X7 X2, X4, X6, X8
Pos : 25.23 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sic herheits hinweise/Ac htung/Ac htung: Höchs te Strombel astbar bei t der Vers .kontakte( Sens oren) und Sens orstromaufnahme 400 mA @ 8\mod_1278305007084_21.doc x @ 58890 @ @ 1
The highest current carrying capacity of the supply contacts is 4 A!
Ensure that the sensors are supplied with power from the U
sensors´ power consumption is to be taken into consideration when determining
the present power demand for the U
The total maximum power consumption of the sensors must not exceed
400 mA!
Please note that the combined power consumption of all connected sensors is not
to exceed 400 mA. The distribution of power among the existing connections is
depending on the individual power requirements of the sensors.
Pos : 25.24 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Connection diagram
IN
supply line.
LS
WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
supply line. The
LS
Manual
Version 2.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

767-1201

Table of Contents