7.2

Switching on the Fieldbus Coupler

The fieldbus coupler starts running immediately when the power supply is
switched on. Depending on how the name assignment for the fieldbus coupler is
to be carried out, the station name may need to be set via the DIP switch before
switching on the power supply.
After an initialization phase, the fieldbus coupler and all I/O modules connected
to it are ready for operation. The fieldbus coupler indicates operational readiness
when the BF LED blinks red. If the fieldbus coupler is not attached to the
ETHERNET network via either the FB1 or FB2 ETHERNET connection, the
BF LED illuminates red. In this state, the fieldbus coupler is not ready for
operation.
Data exchange
A data exchange with the IO Controller can only take place when the station name
of the fieldbus coupler is consistent with the name of the configuration.
Pos : 27.9 /Serie 767 (WAGO-SPEED WAY)/Wic htige Erläuterungen/Sicherheits hinweis e/Hi nweis /Hinweis: Keine 767-Komp. entfernen @ 8\mod_1279526731811_21.doc x @ 60342 @ @ 1
Disruption during operation
None of the 767 Series devices are to be removed or added during operation, as
this causes a disruption in the 767 station.