Table 61: Channel Properties, Type (Bit 0; Table 62 Channel Properties, Group Diagnostic (Bit 8); Table 63: Channel Properties, Maintenance Information (Bit 9; Table 64: Channel Properties, Incident (Bit 11 - WAGO -SPEEDWAY 767 Manual

Profinet io fielbus coupler for wago-speedway 767
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
The channel properties are stored in a 16-bit value and defined as follows in
accordance with the PROFINET specification:

Table 61: Channel properties, type (bit 0 ... 7)

Type
00
H
01
H
02
H
03
H
04
H
05
H
06
H
07
H

Table 62 Channel properties, group diagnostic (bit 8)

Diagnostic
00
H
01
H

Table 63: Channel properties, maintenance information (bit 9 ... 10)

Information
00
H
01
H
02
H
03
H

Table 64: Channel properties, incident (bit 11 ... 12)

Diagnostic
00
H
01
H
02
H
03
H
Manual
Version 2.2.0
Description
The value is to be used in connection with a module-specific diagnostic (channel
number = 8000
) or when the data width of the channel is not specified.
H
Channel-specific diagnostic, channel data width = 1 bit.
Channel-specific diagnostic, channel data width = 2 bits.
Channel-specific diagnostic, channel data width = 4 bits.
Channel-specific diagnostic, channel data width = 8 bits.
Channel-specific diagnostic, channel data width = 16 bits.
Channel-specific diagnostic, channel data width = 32 bits.
Channel-specific diagnostic, channel data width = 64 bits.
Description
This diagnostic can be assigned to the module or to a channel.
This is a group diagnostic that was released by one or more channels.
Description
This diagnostic describes a disruption. The diagnostic incident is defined in bit
11 ... 12.
This diagnostic describes a status of the module in which maintenance is required.
The diagnostic incident is defined in bit 11 ... 12.
This diagnostic describes a status of the module in which maintenance should be
carried out soon. The diagnostic incident is defined in bit 11 ... 12.
This diagnostic describes a disruption. According to the error type, qualified
information is also conveyed.
Description
This diagnostic is no longer available, including the advanced diagnostic
information (maintenance).
A diagnostic has arisen or continues to exist.
This diagnostic is no longer available.
This diagnostic is no longer available, but other error messages are stored in the
diagnostic memory.
PROFINET IO Diagnostics
121

Advertisement

Table of Contents
loading

This manual is also suitable for:

767-1201

Table of Contents