196
Parameterization via WAGOframe
Parameters of Field Supply
Table 106: Adjustable parameters of the field supply
Parameter
Enable field supply
Autorestart delay
Simulation diagnostic
Short circuit/overload
Pos : 56 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
767-1201 FC PROFINET IO 8DI 24V DC
Description
Switch on the field supply (24VDC) for the sensors here.
Default setting: selected
In the event of a short circuit, the sensor supply is switched off for a
parametrizable amount of time. Here, enter the delay time (in
100-ms increments); after this time, the sensor supply is restarted.
If the short circuit still exists, the process is repeated.
The simulation can be used to simulate a short circuit.
Default setting: unselected
If simulation is deactivated, the respective error is displayed upon
emergence.
If simulation is activated, you can simulate one of the errors by
selecting the appropriate parameter.
WAGO-SPEEDWAY 767
Manual
Version 2.2.0