WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
14.4.1
Progression of Blink Sequence
The following table outlines the progression of the blink codes over time. If there
is no number in the second position ("1" in the number "10") or third position
("1" in the number "100") for the group number, error code or error argument, the
subsequent pause does not take place; instead, the next sequence is initiated
(designated in bold and cursive font in the following table).
Table 75: Overview of the blink codes
Description
Start sequence blinks
Pause
Group number
Group number (third (100)
position)
Pause
Group number (second (10)
position)
Pause
Group number (first (1)
position)
Pause
Blinks
Pause
Error code
Error code (third (100)
position)
Pause
Error code (second (10)
position)
Pause
Error code (first (1) position)
Pause
Blinks
Pause
Error argument
Error argument
position)
Pause
Error argument
position)
Pause
Error argument
position)
Pause
Progression restarts when
Manual
Version 2.2.0
Frequency
10 cycles with 12.5 Hz each
(12.5 times per second)
1 s
Repeats: 0.5 s on and 0.5 s off
2 s
Repeats: 0.5 s on and 0.5 s off
2 s
Repeats: 0.5 s on and 0.5 s off
2 s
40 ms
2 s
Repeats: 0.5 s on and 0.5 s off
2 s
Repeats: 0.5 s on and 0.5 s off
2 s
Repeats: 0.5 s on and 0.5 s off
2 s
40 ms
2 s
(third (100)
Repeats: 0.5 s on and 0.5 s off
2 s
(second (10)
Repeats: 0.5 s on and 0.5 s off
2 s
(first (1)
Repeats: 0.5 s on and 0.5 s off
4 s
start sequence
blinks
Diagnostics
Additional explanations
Initiation of start phase
Repeats according to group number
-
Repeats according to group number
-
Repeats according to group number
-
Initiation of error code
Repeats according to error code
-
Repeats according to error code
-
Repeats according to error code
-
Initiation of error argument
Repeats according to error
argument
-
Repeats according to error
argument
-
Repeats according to error
argument
-
135