Table 73: Ethernet Status Messages - WAGO -SPEEDWAY 767 Manual

Profinet io fielbus coupler for wago-speedway 767
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC

Table 73: ETHERNET status messages

LED
BF
DIA
ACT/LNK 1
ACT/LNK 2
Pos : 52.6 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 2.2.0
Color/status
Off
Red
Red, flashing
Green, flashing
Off
Red
Off
Green
Green, flashing
Off
Green
Green, flashing
Cause
The fieldbus coupler is
in the process of
exchanging data.
The fieldbus coupler is
not connected to the
ETHERNET network.
The fieldbus coupler is
connected to the
ETHERNET network
and is not in the process
of exchanging data.
Flashing test is active.
This mode takes
precedence over the
other indicating modes.
As long as it is active
the status of the
PROFINET link is not
indicated by the red
LED.
No diagnostic message
is present.
A diagnostic message is
present.
Fieldbus coupler has no
connection with the
physical network.
Connection to physical
network is present.
Data is being exchanged
via ETHERNET.
Fieldbus coupler has no
connection with the
physical network.
Connection to physical
network is present.
Data is being exchanged
via ETHERNET.
Diagnostics
131
Remedy/information
-
Check the cable connection
of the FB1 and/or FB2
ETHERNET connections.
Check the connection to the
IO Controller and the
configuration
The flashing test is enabled
by a PROFINET command
from the configuration tool.
The test is used to identify a
specific device in the
configuration.
-
Read out the diagnostic
message via your
configuration tool and
resolve the displayed error.
Check the cable connection
of the FB1 ETHERNET
connection.
-
-
Check the cable connection
of the FB2 ETHERNET
connection.
-
-

Advertisement

Table of Contents
loading

This manual is also suitable for:

767-1201

Table of Contents