WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
Table 104: Adjustable parameters of the digital inputs
Parameter
Substitute Value Strategy
Substitute Value
Simulation input value
* Default setting
Global Settings
Table 105: Adjustable parameters for the entire fieldbus coupler
Parameter
Simulation diagnostic
Low voltage U
Low voltage U
Manual
Version 2.2.0
Description
This releases, if the field bus supports, the substitute value or the last
input value in cases such as a fieldbus interruption. You have the
following options:
- Switch to substitute value*
- Retain last value
Enter here the process value that is used in case of an error. In the
case of an error (fieldbus interruption), this value is used with the
"Switch to Substitute Value" substitute value strategy.
Checkbox unselected:
0*
Checkbox selected:
1
This simulation can be used to simulate input values.
Checkbox unselected*:
The value at the inputs is carried over into the process image.
Checkbox selected:
The simulation value is inserted into the process data independent of
the input value. The "Input Value" parameter is selected.
Description
If the checkbox is selected, you can simulate a low voltage
diagnostic. To generate a low voltage diagnostic, one or both of the
two checkboxes "Low voltage U
selected.
Default setting: unselected
In the case of an undervoltage of the logic and sensor supply (U
LS
the actuator supply (U
here.
A
Parameterization via WAGOframe
" and "Low voltage U
LS
), the corresponding diagnostic is displayed
A
195
" must be
A
) or
LS