Connecting The Supply Cable; Table 23: Supply Connection Assignment - WAGO -SPEEDWAY 767 Manual

Profinet io fielbus coupler for wago-speedway 767
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

58
Connecting Data and Supply Cables
Pos : 25.19 /Serie 767 ( WAGO-SPEED WAY)/Ansc hluss D aten- und Versorgungs kabel/F eldbus koppler/Ansc hluss _Spannungs vers orgung @ 7\mod_1268906369493_21.doc x @ 53462 @ 2 @ 1
6.5

Connecting the Supply Cable

The supply cable provides power to the fieldbus coupler and the connected I/O
modules.
Requirement:
A supply cable for +24 VDC and 0 VDC must be connected to the supply
input (6 in the figure on the next page) via appropriate fuses.
The WAGO supply cable pre-assembled on both ends must be available (K1
and K2 in the figure on the following page).
The following table outlines the assignment of the supply connections:

Table 23: Supply connection assignment

Connection
IN
The highest current carrying capacity of the supply contacts is 4 A!
Always observe the maximum current carrying capacity per supply line (U
for each 767 component and the overall power consumption for all 767
components. Neither of these values shall exceed 4A since an increase in current
causes the contacts to overheat and damages the 767 components. Information
regarding the power demand of each 767 component can be found in the
corresponding data sheet, which can be downloaded at www.wago.com.
Contact
OUT
1
2
3
4
WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
Description
24 VDC U
LS
24 VDC U
A
0 V U
LS
0 V U
A
, U
)
LS
A
Manual
Version 2.2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

767-1201

Table of Contents