Example Of An Error Message Via Blink Code - WAGO -SPEEDWAY 767 Manual

Profinet io fielbus coupler for wago-speedway 767
Hide thumbs Also See for WAGO-SPEEDWAY 767:
Table of Contents

Advertisement

136
Diagnostics
14.4.2

Example of an Error Message via Blink Code

The following example clarifies an error message as indicated by the blink code.
An S-BUS error is displayed when the software update for the sixth I/O module
fails.
Initialization:
1.
The CS LED begins with the initiation of the start phase: quick flashing of
about 1 s
2.
A one-second pause occurs.
Group number 1: S-BUS error
3.
The CS LED blinks once for the first digit: 0.5 s on and off.
4.
The initiation of the error code follows with a pause of two seconds, 40ms
of blinking and another pause of two seconds.
Error code 13: software update for I/O module failed
5.
The CS LED blinks once for the first digit.
6.
A two-second pause occurs.
7.
The CS LED blinks 3 times for the second digit.
8.
The initiation of the error argument follows with a pause of two seconds,
40ms of blinking and another pause of two seconds.
Error argument 5: I/O module in the sixth slot
9.
The CS LED blinks 5 times for the first digit.
10.
A four-second pause occurs.
The blink code starts when the start phase is initiated. This process is repeated if
only one error is present; if more are present, the next pending error is processed.