Expanded Standard Error Types

Expanded standard error types provided additional information about errors that
are not sufficiently described by the standard error types 1 through 9 due to the
definitions in the PROFINET specification. For a detailed description of the error,
the fieldbus coupler therefore utilizes the error type 258 instead of types 1 through
9. The expanded error type provides a more specific description of the error.

Table 70: Expanded standard error types and description

Error type
258
258
258
258
258
258
259
513
513
513
513
514
514
Pos : 47 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 2.2.0
Expanded
Description
error type
1
Undefined failure
2
Undervoltage ULS (Logic/Sensor)
3
Undervoltage UA (Actor)
4
Load error (short circuit/line break)
5
Short circuit field supply
6
Open load field supply
1
Setting modules into RUN mode failed
262
Restart the coupler, please!
267
Restart the coupler, please!
518
Break after module of slot x
523
Communication error
260
Update process is completed, please wait
516
Module firmware will be updated
PROFINET IO Diagnostics