52
Connecting Data and Supply Cables
Pos : 25.11 /Serie 767 ( WAGO-SPEED WAY)/Ansc hluss D aten- und Versorgungs kabel/F eldbus koppler/0_Ansc hlus s_F eldbus kabel anschli eßen - Übersc hrift 2 @ 8\mod_1281001995154_21.doc x @ 62338 @ 2 @ 1
6.3
Connecting the Fieldbus Cable
Pos : 25.12 /Serie 767 ( WAGO-SPEED WAY)/Ansc hluss D aten- und Versorgungs kabel/F eldbus koppler/Ansc hluss _ETHERN ET-Kabel 767- 1201 Ei nlei tung @ 8\mod_1279518663025_21.doc x @ 60306 @ @ 1
To set up a connection with an IO Controller, the fieldbus coupler must be
connected to a network with a transfer rate of 100 Mbit/s in full-duplex mode.
Pos : 25.13 /Serie 767 ( WAGO-SPEED WAY)/Ansc hluss D aten- und Versorgungs kabel/F eldbus koppler/Ansc hluss _ETHERN ET-Kabel 767- 1201/1301/2301 @ 8\mod_1279518634586_21.doc x @ 60302 @ 33 @ 1
The following table outlines the connection assignments for the ETHERNET
connections:
Table 21: ETHERNET connection assignments
Connection
If you do not use a pre-assembled ETHERNET cable, a shielded M12 plug with
the IP 67 degree of protection is to be connected to this.
To connect a cable which is pre-assembled on one end only to an RJ-45 plug,
proceed as follows:
Contact Connection Color
1
2
3
4
Because the Auto MDI(X) functionality for the respective ETHERNET
connection FB1 or FB2 is activated, a cross-over cable is not necessary. This
functionality automatically detects the direction for sending data and receiving
data so that it is irrelevant which cable type is used (crossed or uncrossed).
Contact
IN
1
2
3
4
Connecting thread
TX+
Yellow
RX+
Blue
TX-
Brown
RX-
White
WAGO-SPEEDWAY 767
767-1201 FC PROFINET IO 8DI 24V DC
Description
TX+
RX+
TX-
RX-
Shielded
Contact of RJ-45 plug
1
2
3
6
Manual
Version 2.2.0