In order to prevent a malfunction caused by interference voltage supply on the control
inputs, the following directions should be observed:
Å Use shielded/drilled cables
Å Lay shield on one side of the inverter onto earth potential
Å Lay control and power cable separately (about 10...20 cm apart)
Å Lay crossings in a right angle (in case it cannot be prevented)
EMC
Use of internal voltage supply
X2A
Use of external voltage supply
X2A
13...30V DC ±0%
smoothed
Ri =2,1 kΩ
Connect unused analog inputs to common, to prevent set value fluctuations!
External analog
set-point setting
Ri = 55 kW
X2A
1 2 3 4 5 6 7 8 9
+
0...±10 VDC
*) Connect potential equalizing line only
if a potential difference of > 30 V exists
between the controls. The internal
resistance is reduced to 30 kΩ.
Date
Name: Basis
18.05.04
KEB COMBIVERT F5-M / S
10 11 12 13 14 15
16 17
10 11 12 13 14 15
16 17
PE
X2A
*
Control Cards
20 21 22 23
PE
23
+
20...30 VDC
Internal analog
set-point setting
1 2 3 4 5 6 7 8 9
R = 3...10 kW
©
KEB Antriebstechnik, 2002
All Rights reserved
PE