Locking Of Parameter Sets; Parameter Set On/Off Delay (Fr.5, Fr.6) - KEB COMBIVERT F5 MULTI Applications Manual

Hide thumbs Also See for COMBIVERT F5 MULTI:
Table of Contents

Advertisement

Functional Description
6.8.8
Locking of Para-
meter Sets
Fr.3 Parameter set lock
6.8.9 Parameter Set
ON/Off Delay
(Fr.5, Fr.6)
Fig. 6.8.9
ON and OFF-delay
Example
on
off
Set
Fr.5
Fr.6
0
0 s
0 s
1
2 s
0 s
2
0 s
1 s
3
2 s
2 s
Chapter
Section
Page
6
8
8
Parameter set, that shall not and must not be selected, can be locked with Fr.3. If one
of the locked sets is selected, the inverter switches off with set selection error (E.SEt).
Value
1
2
4
8
16
32
64
128
Set 2 and Set 5 locked
With these parameters the time is adjusted,
- with which the activation of a new set is delayed (Fr.5)
- with which the deactivation of an old set is delayed (Fr.6)
In the case of set changeover the OFF time of the old set and ON time of the new set
are added up.
Set 3
Set 2
Current set
Set 1
Set 0
Set 3
Set 2
Adjusted set
Set 1
Set 0
Date
Name: Basis
KEB COMBIVERT F5
05.05.04
Locked set
Example
0
-
1
-
2
4
3
-
4
-
5
32
6
-
7
-
Sum
36
1
2
3
1:
ON delay for set 3 of 2s
2:
OFF delay for set 3 of 2s
3:
OFF delay for set 2 of 1s +
ON delay for set 1 of 2 s
4:
immediate changeover as no delay is adjusted
5:
OFF delay for set 2 of 1s +
ON delay for set 3 of 2s
6:
OFF delay for set 3 of 2s
Parameter Sets
5
4
©
KEB Antriebstechnik, 2002
All rights reserved
6