Special Functions
Motor potentiometer value
(oP .52)
Source of Setpoint (oP.0) and
Direction of rotation (oP.1)
Used Parameters
PROG.
Param.
Adr.
RO
ru.37
0225h
-
oP.0
0300h
-
oP.1
0301h
-
oP.50
0332h
-
oP.52
0334h
-
oP.53
0335h
-
oP.54
0336h
-
oP.55
0337h
-
oP.56
0338h
-
oP.57
0339h
-
oP.58
033Ah
-
oP.59
033Bh
-
©
KEB Antriebstechnik, 2002
All rights reserved
With this parameter a value in percent can be adjusted within the preset limits directly
by operator or bus. The ramp time (oP.59) remains unconsidered at this setting.
In order to preset the setpoint by way of the motor potentiometer, oP.0 (setpoint source)
must be set to value „4". The source of rotation direction (oP.1) must be adjusted in
dependence on the setpoint (value „6" or „7").
If the motor potentiometer is used as setpoint source, the setpoint is calculated from
this with the respective limits just as with other percental setpoint sources (see Chapter
6.4. „Set Value Adjustment").
ENTER
min
-
-
-100.00 %
100.00 %
0
0
-
0
-
-100,00 %
100,00 %
-
-
-100,00 %
100,00 %
-
-
-100,00 %
100,00 %
-
-
-100,00 %
100,00 %
-
0
4095
-
0
4095
-
0
4095
-
-
0,00 s
50000,00 s
Name: Basis
KEB COMBIVERT F5
Functional Description
Step
max
default
0.01 %
-
9
1
0
9
1
2
3
1
0
0,01 %
0,00 %
0,01 %
0,00 %
0,01 %
100,00 %
0,01 %
0,00 %
1
0
1
0
1
0
0,01 s
66,00 s
-
„4" for motor potentiometer
„6 and 7" rotation direct. over setpoint
-
-
-
-
-
-
-
-
-
Date
Chapter
Section
6
9
04.05.04
6
Page
9