Initial Start-up
7.2.3
Adjustment
Assistance
Speed Controller
Problem: Very long transient process, but stabilization
during constant run
Solution: Increase P-fraction (cS.6); eventually reduce
I-fraction (cS.9)
Problem:
Sustained oscillation short billowy, noises,
vibes
Solution:
Decrease P-fraction (cS.6)
Problem:
Overshoot too long, strong speed
decreases at load change
Solution:
Increase I-fraction (cS.9)
©
KEB Antriebstechnik, 2002
All Rights reserved
After initial start-up the following adjustments must be done:
Switch off control release (terminal X2A.16) ⇒ Inverter in status ÑnoPì
1.
2.
Select regulated operation
3.
Adjust speed controller
Name: Basis
KEB COMBIVERT F5-M / S
Start-up
⇒ Parameter cS.0
⇒ see adjustment tips below
Problem:
Speed overshoot too high
Solution:
Increase P-fraction (cS.6); eventually
reduce I-fraction (cS.9)
Problem:
Transient too slow / remaining system
deviation
Solution:
Increase I-fraction (cS.9)
Problem:
Sustained oscillation long billowy
Solution:
Reduce I-fraction (cS.9) and / or reduce
P-fraction (cS.6)