4 Connection of the control

Observe the following instructions to avoid malfunctions!
– Install control cables and power cables separately (approx. 10...20 cm dis-
tance); Lay crossings in a right angle.
– In case of inductive load on the relay outputs a protective wiring must be
provided (e.g. free-wheeling diode).
– Electro magnetic interferences can be prevented by the following measures:
– Always use twisted and shielded cables for analog control lines. Connect
the shield at one side at the signal source.
– Twist digital control cables. Up from 3 m a shield may be required. In this
case connect the shield at both ends.
– Connect the shield of the brake and temperature monitoring together with
the motor shield. Leave the inner shields longer in order to avoid interfer-
ence coupling or decoupling (the latter during temperature measurement)
as far as possible.
The terminals of the control terminal block, enocder inputs and communication in-
terface are securely isolated in accordance with

4.1 Assembly of wires

Loose and slack cable connections!
Malfunctions due to loose contacts.
a) Observe metal sleeve length and stripping length according to table.
b) Use a suitable pressing tool.
c) Make sure that all wires are inserted into the wire-end sleeve.
d) After inserting the cable into the terminal, check that it is firmly seated.
Cross-section
0.5 mm²
0.75 mm²
1.0 mm²
1.5 mm²
0.2...1.5 mm²
ein- oder
feindrähtig
Table 8: Wire-end ferrules and stripping length
Connection of the control | 4
Wire-end ferrule
Metal sleeve
with plastic collars
without plastic col-
lars
without wire-end
ferrule
EN
61800-5-1.
Stripping length
length
10 mm
12 mm
12 mm
14 mm
12 mm
15 mm
10 mm
10 mm
-
10...12 mm
17