Technology Controller; The Pid Controller - KEB COMBIVERT F5 MULTI Applications Manual

Hide thumbs Also See for COMBIVERT F5 MULTI:
Table of Contents

Advertisement

Technology Control
6.12 Technology
Controller
6.12.1 The PID Control-
ler
Pic. 6.12.1 PID controller
Set value calculation
Actual value calculation
PID controller KP (cn.4)
PID controller KI (cn.5)
PID controller KD (cn.6)
PID positive limit (cn.7)
PID negative limit (cn.8)
PID fade-in time (cn.9)
©
KEB Antriebstechnik, 2002
All rights reserved
The KEB COMBIVERT is equipped with a universally programmable technology
controller, with it pressure, temperature or dancing position controls can be set up.
The technology controller consists of a set/actual value comparator, that puts the
system deviation on a PID controller. With cn.4, 5 and 6 the P-, I- and D component is
adjustable. The parameters cn.7 and cn.8 limit the maximum manipulated variable of
the controller. With the PID-controller fade-in time (cn.9) the controller amplification
can be driven up gently from 0...100%. Parameter cn.14 adjusts the frequency reach-
through ins Hz/% (only
the I-Controller and/or the controller fade-in can be reset. With cn.10 a PID-reset condition
can be adjusted.
PID controller
cn.4 PID kp
cn.5 PID ki
cn.6 PID kd
+
-
cn.11 Reset PID /
cn.12 Reset I /
input selection
input selection
Defines the proportional amplification factor in the range of 0,00...250,00.
Defines the integral amplification factor in the range of 0,000...30,000.
Defines the differential amplification factor in the range 0,000...250,00.
The max. positive manipulated variable is determined with cn.7 in the range of
-400,0...400,0 %, the max. negative manipulated variable is determined with cn.8 in
the range of -400,0...400,0 %.
With it the control action during the start can be increased linear or decreased linear at
the reset of the fade-in. The time refers of 100% of the controller output value. If one
input is programmed for „Reset fade-in" (cn.13) the fade-in is counted down at active
input and counted up at inactive input.
Value range: -0,01; 0,00 ... 300 s; Resolution: 0,01 s
With the setting „-0.01" the fade-in is calculated according to following formula:
Fade-in factor = f_setting (ru.2) / max. setpoint value (o.P10/11)
The function is only active, if the technology controller is used as process controller
(cs.0 Bit 0...2 = 1). With the adjustment as setpoint controller the fade-in time is 0.
Name: Basis
KEB COMBIVERT F5
Functional Description
F5-G/B).
Over parameter cn.11, 12 and 13 the PID-Controller,
cn.9 PID
fading time
v
cn.7
cn.8
t
cn.10 PID Reset
condition
cn.13 Fade in
reset / input
selection
Digital inputs
04.05.04
ru.52
oP.0
cn.14
%
cS.0
Hz
Date
Chapter
Section
6
12
6
Page
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combivert f5 servo

Table of Contents