Functional Desription
Bus synchron time
Sy. 8
Adr.
0008h
The time, within which the control synchronized onto an external clock pulse (sercos), is entered in this parameter. If
no sychnronization takes place, an error or status message (E.SbuS or A.SbuS) , depending on the adjusted
behaviour, is output. The value Ñoffì deactivates the function.
HSP5 Watchdaog time
Sy. 9
Adr.
0009h
The HSP5 Watchdog-function monitores the communication of the HSP5-interface (control card - operator; or control
card - PC). After expiration of an adjustable time (0,01...10 s) without incoming telegrams, the response adjusted in Pn.5
is triggered. The value Ñoffì deactivates the function.
Baud rate int. bus
Sy. 11
Adr.
000Bh
With the internal baudrate the transmission rate between operator and inverter is determined. Following values are
possible:
Value
Baudrate
3
9,6 kBaud
4
19,2 kBaud
5
38,4 kBaud
After Power-On it is always started with 38.4 kBaud and dependent on the operator higher set.
Scope timer
Sy. 32
Adr.
0020h
The scope timer generates a time period of 1 ms. This can be used by external programs, e.g. Scope, to represent time
patterns. The timer counts from 0...65535 and starts again with 0 after an overflow.
Control word high
Sy. 41
Adr.
0029h
The control word is used for the status control of the inverter via bus. The control word long (Sy.43) consists of the two
16 bit parameters control word high (Sy.41) and Control word low (Sy.50). The status word is bit-coded. The description
of the individual bits is found in Chapter 11.2.7.
Chapter
Section
Page
6
1
26
min
max
0 (off)
65000
min
max
0 (off)
10,00
min
max
3
11
Value
Baudrate
Value
6 55,5 kBaud
7 57,6 kBaud
8
100 kBaud
min
max
0
65535
min
max
0
65535
Date
Name: Basis
KEB COMBIVERT F5-M / S
12.05.04
1
0,01
1
Baudrate
*)
9
115,2 kBaud
10
125 kBaud
11
250 kBaud
1
1
Operating and Unit Data
default
µ µ µ µ µ s
0 (off)
default
s
0 (off)
default
-
11
*) at F5-M not possible
default
-
0
default
-
0
©
KEB Antriebstechnik, 2002