Setpoint Calculation - KEB COMBIVERT F5 MULTI Applications Manual

Hide thumbs Also See for COMBIVERT F5 MULTI:
Table of Contents

Advertisement

Setpoint- and Ramp Adjustment
Fig. 6.4.5.a Setpoint limits
Setpoint [%]
Maximal value
reverse
6.4.6

Setpoint Calculation

©
KEB Antriebstechnik, 2002
All Rights reserved
+n [rpm]
(oP. 10)
(oP.14)
-100%
-n [rpm]
The unit differentiates between two setpoint adjustments:
ï
the setpoint adjustment in percent
With the adjusted setpoint limits the speed range 0%...100% is defined. In
this case the adjustment 0% corresponds to the minimal speed and 100%
to the maximal speed. The speed after the setpoint limiting is calculated
according to following formula:
positive setpoint = oP.6 + (setpoint adjustment [%] x
negative setpoint = oP.7 + (setpoint adjustment [%] x
ï
the absolute setpoint adjustment, i.e. the setpoint is directly adjusted as
speed and limited through the corresponding minimal and maximal values
as well as through the absolute maximal value.
The setpoint sources are assigned as follows:
Setpoint adjustment in percent
Terminal strip (analog setpoint)
Keyboard/Bus in %
Motorpoti
Technology controller
Name: Basis
KEB COMBIVERT F5-M / S
Functional Desription
+100%
(oP.11)
Absolute setpoint adjustment
Keyboard/Bus absolute
Set speed value SY.52
Speed measurement
Date
12.05.04
Maximal value
forward
Absolute maximal
value forward
Setpoint[%]
oP.10-oP.6
)
100%
oP.11-oP.7
)
100%
Chapter
Section
Page
6
4
13
6