CONNECTION OF THE POWER UNIT

5.2.5.8 Connection of the temperature monitoring and brake control (X1C)

A switchable temperature evaluation is implemented in the COMBIVERT.
There are different types for the evaluation available. These are dependending on the
control board =>
The desired operating mode can be adjusted via software (dr33). If the evaluation is
not required, it must be deactivated via software (parameter pn33 = 7) =>
manual
X1C
2
4
6
1
3
5
Figure 25:
Terminal block X1C for control board APPLICATION and COMPACT
X1C
2
4
6
8
10
1
3
5
7
9
Figure 26:
Terminal block X1C for control board PRO
NOTICE
64
instruction manual „control
PIN
Name
1
BR+
2
BR-
3
reserved
4
reserved
5
TA1
6
TA2
PIN
Name
1
BR+
2
BR-
3
0V
4
24Vout
5
DIBR1
6
DIBR2
7
reserved
8
reserved
9
TA1
10
TA2
Malfunctions due to incorrect line or laying!
Malfunctions of the control due to capacitive or inductive coupling.
► Do not route cables from the motor temperature sensor (also shiel-
ded) together with control cables.
► Cables from the motor temperature sensor within the motor cables
may only be used with double shielding!
► The input of the temperature detection has basic isolation.
board".
Description
Brake control / output +
Brake control / output -
Temperature detection / output +
Temperature detection / output -
Description
Brake control / output +
Brake control / output -
For supply of the checkback inputs
Checkback input 1 for brake and relay
Checkback input 2 for brake and relay
Temperature detection / output +
Temperature detection / output -