Special Functions
6.9.4
Timer and
Counter
Fig. 6.9.5
Timer programming
I3
LE.21 Timer 1 / Mode
I4
LE.26 Timer 2 / Mode
Timer / Mode (LE.21/26)
Input I3 => Timer 1
Input I4 => Timer 2
©
KEB Antriebstechnik, 2002
All rights reserved
Two timers are incorporated in the COMBIVERT. As long as one of the adjustable
starting conditions (LE.18/23) or a programmable input (LE.17/22) is set, the timer
counts until reaching the final range value. If one of the reset conditions (LE.20/25) is
fulfilled or one programmable input (LE19/24) is set, the timer jumps back to zero. The
resolution, whether the timer works in seconds or hours, is adjusted with LE.21/26.
The current timer content is displayed in ru.43/44. On reaching an adjustable comparison
level (LE.0...7), the switching condition 37/38 is set. It can be used to set an output.
continues to count
Timer counts up to
maximum value if a
condition of LE.18 is fulfilled
or an input of LE.17 is set!
ru.43 Current counter content
Resetting to zero
continues to count
Timer counts up to
maximum value if a
condition of LE.23 is fulfilled
or an input of LE.22 is set!
ru.44 Current counter content
Resetting to zero
LE.21 and LE.26 determine the clock source and the counting direction of timer 1 and
timer 2. Clock source can be the time counter in 0.01 s or h-raster or impulses from an
input. The timer runs generally as long as a starting condition is active. After a reset
the timer starts again at zero. The timer stops at the maximal value of 655.35. Following
clock sources can be selected:
Bit
Value Function
0...2
Clock source
0
Time counter 0,01 s (default)
1
Time counter 0,01 hour
2
Edge counter, each edge increases/decreases the counter by 0.01
3
Edge counter, only positive edges increase/decrease the counter by 0.01
4...7 reserviert
3...5
Counting direction
0
Upward
8
The counting direction is dependent on direction of rotation (FOR=upward;
REV=downward)
16
The counting direction is dependent on direction of rotation (REV=upward;
FOR=downward)
The values from Bit 0...2 and 3...5 are to be added up.
Name: Basis
KEB COMBIVERT F5
Functional Description
Is a
no
reset condition
Timer value > level
of LE.20 or LE.19
LE.0...LE.7 ?
fulfilled?
yes
Is a
no
reset condition
Timer value > level
of LE.25 or LE.24
LE.0...LE.7 ?
fulfilled?
yes
no
yes
Switching cond. 37
„Timer 1 > Level A"
is being set!
no
yes
Switching cond. 38
„Timer 2 > Level A"
is being set!
Date
Chapter
Section
6
9
04.05.04
6
Page
11