Installation
4.1.2
EMC
4.1.3
4.1.4
GB - 18
Connection of the Control
In order to prevent a malfunction caused by interference voltage supply on the
control inputs, the following directions should be observed:
- Use shielded/drilled cables
- Lay shield on one side of the inverter onto earth potential
- Lay control and power cable separately (about 10...20 cm apart)
- Lay crossings in a right angle (in case it cannot be prevented)
Digital Inputs
Use of internal voltage supply
4
5
6
7
10 11
Use of external voltage supply
4
5
6
7
10 11
Analog Inputs
setting (see CP.24)
16 17 18
PE
R = 3...10 kΩ
0...10 V DC
+
Ri = 4 kΩ
0(4)...20 mA DC
+
Ri = 250 Ω
Connect unused analog inputs to common, to prevent set value fluctuations!
13 14
19 20
13 14
19 20
+
13...30 V DC
set-point setting
8
9
+
-
SPS
PE
13...30 V DC
±0 % smoothed
Ri = 4,4 kΩ
PE
PE
18
0...±10 V DC
Ri = 40 kΩ