KEB COMBIVERT F5 MULTI Applications Manual page 27

Hide thumbs Also See for COMBIVERT F5 MULTI:
Table of Contents

Advertisement

Product Description
2.1.8
Overload curve
Curve 1
Time [s]
300
270
240
210
180
150
120
90
60
30
0
105 110 115 120 125 130 135 140 145 150 160
The characteristic declines device-dependently in this range (see technical data)
On exceeding a load of 105 % the counter starts. When falling below the counter counts backwards. If the counter
achieves the overload characteristic that corresponds to the inverter the error E.OL is triggered.
2.1.9
Overload protection in the lower speed range
(only valid for F5-M and F5-S, stall current see technical data)
OC-tripping current
Short-time limit current
Start of overload
integrator at 105%
Stall current
If the permissible current is exceeded a PT1-element (τ =280ms) starts, after its sequence of operation the error E.OL2 is
triggered.
©
KEB Antriebstechnik, 2002
All Rights reserved
Load [%]
170 180 190 200 210 220
Load [%]
E.OL2
Name: Basis
KEB COMBIVERT F5
Summary
Curve 2
Time [s]
300
270
240
210
180
150
120
90
60
30
0
105 110 115 120 125 130 135 140 145 150
E.OL
Min. frequency at
continuous full load
Date
Chapter
2
04.05.04
2
Load [%]
f [Hz]
Section
Page
13
1
13