LMX Chassis Connections

WARNING
!
Installation must be completed by qualified service personnel only.
All installation procedures must be performed in accordance to
the information specified in
To run power to the LMX chassis, complete the following steps:
1. Disconnect the power source. Remove the protective cover from the power connections.
2. Ground the chassis to Frame Ground per the following guidelines:
CAUTION
!
The Power wire must not be a heavier gauge than the Ground wire.
Frame Ground can be connected with 8–10 AWG wire (8 AWG
recommended), or in accordance with standard company
requirements. Up to 6 AWG wire can be accommodated with the
appropriate lug.
For correct termination polarity, the –48 VDC voltage potential
must be terminated on the
be terminated on the
NOTICE
If only single-feed power is to be supplied, A and B power feeds must
be wired together to avoid a standing alarm. If A and B power are
both provided, both must be of the same voltage potential.
3. Run power connections to the chassis for A and B power, and terminate them on the power
lugs located at the bottom center of the chassis, per the following guidelines:
CAUTION
!
Use 12 AWG for distances less than 6 feet.
Use 10 AWG for distances greater than 6 feet.
WARNING
!
Do not re-insert fuses at this time. Finish wiring all chassis
connections before applying power to the chassis.
4. Replace the cover over the power connectors.