OPTI-6100 Installation and Turn-Up Practice
9. Check the Major Audible Relay.
a. Toggle the
Major Audible Relay
b. Verify that the Alarm Relay Concentrator indicates a major audible alarm for the proper
chassis location.
c. Toggle the Major Audible Relay off.
d. Verify that the alarm indication clears on the Concentrator.
10. Check the Major Visual Relay.
a. Toggle the
Major Visual Relay
b. Verify that the Alarm Relay Concentrator indicates a major visual alarm for the proper
chassis location.
c. Toggle the Major Visual Relay off.
d. Verify that the alarm indication clears on the Concentrator.
11. Check the Minor Audible Relay.
a. Toggle the
Minor Audible Relay
b. Verify that the Alarm Relay Concentrator indicates a minor audible alarm for the proper
chassis location.
c. Toggle the Minor Audible Relay off.
12. Verify that the alarm indication clears on the Concentrator. Check the Minor Visual Relay.
a. Toggle the
Minor Visual Relay
b. Verify that the Alarm Relay Concentrator indicates a minor visual alarm for the proper
chassis location.
c. Toggle the Minor Visual Relay off.
d. Verify that the alarm indication clears on the Concentrator.
13. Logout of the OPTI-6100 System.
a. Press
until the top level chassis menu is displayed.
E
SC
b. Select
, and press
Logout
14. Restore the Alarm Relay Concentrator
If the Alarm Relay Concentrator was re-provisioned in step 6, restore the provisioning by
taking the input ports for all of the chassis out of the Out of Service or Test mode.
15. Verify that the Concentrator shows no alarm states for the chassis.
A-10
on.
on.
on.
on.
.
E
NTER
61184500L1-5L