Connect Chassis Power and Ground
The following sections detail the wiring for the different OPTI-6100 chassis.
MX Chassis Connections
WARNING
!
Installation must be completed by qualified service personnel only.
♦
All installation procedures must be performed in accordance to
♦
the information specified in
To run power to the MX chassis, complete the following steps:
1. Disconnect the power source. Remove the protective cover from the power connections.
2. Ground the chassis to Frame Ground per the following guidelines:
CAUTION
!
The Power wire must not be a heavier gauge than the Ground wire.
♦
Power connections can be made with 14–18 AWG wire. ADTRAN
♦
recommends a minimum of 16 AWG.
Frame Ground can be connected with at least 14 AWG wire, or in
♦
accordance with standard company requirements. Up to 6 AWG
wire can be accommodated with the appropriate lug.
For correct termination polarity, the ±24 VDC or –48 VDC voltage
♦
potential must be terminated on the
potential must be terminated on the
NOTICE
If only single-feed power is to be supplied, A and B power feeds must
be wired together to avoid a standing alarm. If A and B power are
both provided, both must be of the same voltage potential.
3. Run power connections to the chassis for A and B power, and terminate them on the power
lugs located on the upper right corner of the chassis rear panel. See
WARNING
!
Do not re-insert fuses at this time. Finish wiring all chassis
connections before applying power to the chassis.
4. Replace the cover over the power connectors.
61184500L1-5L
"Compliance"
on page 9.
lug and the ground
IN
lug.
RET
Chassis Installation
Figure 5
on page 13.