Capogee Fln Point Database; Apogee Fln Point List Summary - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

C
APOGEE FLN Point Database
This section shows the APOGEE FLN point database for Application 2721.

APOGEE FLN Point List Summary

This database is for APOGEE FLN Application 2721 and features 97 logical points: 29 Logical Analog Inputs (LAI), 35
Logical Analog Outputs (LAO), 19 Logical Digital Inputs (LDI) and 14 Logical Digital Outputs (LDO). These points configure,
control or monitor the operation of the drive.
Information to consider when referencing this table:
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in bold italic type (e.g. 03) can be unbundled at the field panel.
Point
Point
Numb
Point Name
ype
er
CTLR
1
LAO
ADDRESS
2
LAO
APPLICATION
LAI
FREQ OUTPUT
03
LAI
PCT OUTPUT
04
LAI
SPEED
05
LAI
CURRENT
06
LAI
TORQUE
07
LAI
POWER
08
LAI
DRIVE TEMP
09
LAI
DRIVE KWH
10
LAI
MWH
11
LAI
RUN TIME
12
LAI
DC BUS VOLT
13
LAI
AC OUT VOLT
14
15
LAI
PAR N9.01
LAI
RUN TIMEX10K
16
LAI
FAULT CODE
17
LDI
MINOR FLT
18
LDI
MAJOR FLT
19
20
LAO
OVRD TIME
LDI
FWD.REV
21
LDO
CMD REV.STOP
22
LDI
RUN.STOP
23
LDO
CMD RUN.STOP
24
LDI
ZERO SPEED
25
LDI
SPEED AGREE NO AGR
26
LDI
DRIVE READY NOTRDY
27
LDI
LOC.REM MON REMOTE
28
LDO
DAY.NGT
29
30
LAO
CURRENT LMT
31
LAO
ACCEL TIME
32
LAO
DECEL TIME
33
LDO
LOCK PANEL
able C
APOGEE FLN Application 2721 Point Number Summary
Factory
Slope
De ault
En
Units
(SI
(SI Units)
Units)
Units)
31
0
Hz
0
%
0
RPM
0
A
0
%
0
kW
0
° C/F
0
kWh
0
MWh
0
h
0
V
0
V
0
A
0
10Kh
0
NO FLT
NO FLT
1
h
FWD
STOP
STOP
STOP
OFF
DAY
0
A
0
s
0
s
UNLOCK
Intercept
(SI
On e t
(SI Units)
1
0
1
0
0.01
0
0.01
0
1
0
0.01
0
0.1
0
0.1
0
1
0
0.1
0
1
0
1
0
1
0
0.1
0
0.01
0
1
0
1
0
1
0
FAULT
1
0
FAULT
1
0
1
0
REV
1
0
REV
1
0
RUN
1
0
FWD
1
0
ON
1
0
AGREE
1
0
READY
1
0
LOCAL
1
0
NGT
0.01
0
0.1
0
0.1
0
1
0
LOCK
C
APOGEE FLN Point Database
O
e t
Parameter
NO FLT
U1-12 (Bit 6)
NO FLT
U1-12 (Bit 7)
FWD
U1-12 (Bit 2)
STOP
STOP
U1-12 (Bit 0)
STOP
OFF
U1-12 (Bit 1)
NO AGR
U1-12 (Bit 4)
NOTRDY
U1-12 (Bit 5)
REMOTE
DAY
UNLOCK
H5-01
U1-02
U1-03
U1-08
U4-08
U4-10
U4-11
U4-01
U1-07
U1-06
n9-01
U4-01
U2-01
E2-01
C1-01
C
C1-02
1