YASKAWA CIMR-ZU A Series Programming Manual page 140

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 11 S Special Parameters
Mon
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
S2 1/S2
/S2 11/S2 1
Sets the start times for timers 1 to 4.
If the Stop Time is set to a higher value than the Start Time, the Sequence Timers will be active starting from the set Start
Time, run through midnight, and stop the following day at the set Stop Time.
Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer in drive software
Note:
versions PRG: 8551 and earlier.
No
S2-01
S2-06
S2-11
S2-16
<1> Default is 00:00 and range is 00:00 to 24:00 when o4-20 is set to 1 (24-hour).
S2 2/S2 7/S2 12/S2 17 Se uence imers 1 to
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No
S2-02
S2-07
S2-12
S2-17
1
Tue
Wed
Sequence Timer 1
Run at d1-01
Sequence Timer 2
Run at d1-02 with PI control disabled
Fi ure 1 7
Se uence imer E ample
Se uence imers 1 to
Name
Sequence Timer 1 Start Time
Sequence Timer 2 Start Time
Sequence Timer 3 Start Time
Sequence Timer 4 Start Time
Name
Sequence Timer 1 Stop Time
Sequence Timer 2 Stop Time
Sequence Timer 3 Stop Time
Sequence Timer 4 Stop Time
Thur
Fri
Sequence Timer 3
Start ime
Settin
12:00AM to 11:59PM
12:00AM to 11:59PM
12:00AM to 11:59PM
12:00AM to 11:59PM
Stop ime
Settin
00:00 to 24:00
00:00 to 24:00
00:00 to 24:00
00:00 to 24:00
Sat
Sun
Run at d1-03
an e
De ault
12:00AM
<1>
12:00AM
<1>
12:00AM
<1>
12:00AM
<1>
an e
De ault
00:00
00:00
00:00
00:00
<1>
<1>
<1>
<1>