Device Object - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Ob ect ID
BV21
BV22
BV23
BV24
BV25
BV26
BV27
BV28
BV29
BV30
BV31
BV32
BV33
BV34
BV35
BV36
BV37
BV38
BV39
BV40
BV41
BV42
BV43
BV44
BV45
BV46
BV47
BV48
BV49
BV50
BV51
BV52
BV53
BV54
BV55
<1>
BV56
<1>
BV57
<1>
Refer to Accessing Drive Parameters and the Enter Command on page 300
listed in the analog or binary objects.
De ice Ob ect
The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the
Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit value that can range from 0 to
4,194,303. It is configurable by parameters H5-14 and H5-15. Any changes to these parameters will not take effect until the
power is cycled to the drive.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character string. It is writable from the
BACnet network. Any new string written will not take effect until the power is cycled to the drive.
Ob ect Name
Drive Overheat
Fuse Blown
PI Feedback Loss
External Fault
Hardware Error
Mtr Ovrld-OvrTorque
Overspeed
Main CKT Undervoltage
MCU, Cntl Pwr Sy Err
Output Phase Loss
Communication Error
Operator Disconnect
Operating
Aero Speed
Frequency Agree
Desired Frequency Agree
Frequency Detect 1
Frequency Detect 2
Drive Startup Complete
Low Voltage Detect
Base Block
Frequency Reference Mode
Run Command Mode
Overtorque Detect
Frequency Refer Lost
Retry Error
Modbus Comms Error
Modbus Timeout Error
CRC Error
Invalid Data Length
Parity Error
Overrun Error
Framing Error
Timeout Error
Parameter Accept
Parameter Enter
Drive Comm Error
Modbus
Acti e e t
Address
0021H:bit 3
OH1-OH2
0021H:bit 5
PUF
0021H:bit 6
FBL
0021H:bit 7
EF0-EF
0021H:bit 8
CPF
0021H:bit 9
OL1-OL3
0021H:bit 10
OS-DEV
0021H:bit 11
UV
0021H:bit 12
UV1-2-3
0021H:bit 13
LF
0021H:bit 14
CE
0021H:bit 15
OPR
002CH:bit 0
OPERATING
002CH:bit 1
ON
002CH:bit 2
ON
002CH:bit 3
ON
002CH:bit 4
ON
002CH:bit 5
ON
002CH:bit 6
ON
002CH:bit 7
ON
002CH:bit 8
ON
002CH:bit 9
COM
002CH:bit 10
COM
002CH:bit 11
ON
002CH:bit 12
ON
002CH:bit 13
ON
002CH:bit 14
ON
002CH:bit 15
ON
003DH:bit 0
ON
003DH:bit 1
ON
003DH:bit 3
ON
003DH:bit 4
ON
003DH:bit 5
ON
003DH:bit 6
ON
0910H:bit 0
ON
0900H:bit 0
ON
-
ON
for an explanation of how to read and write drive parameters not
B 7 BACnet Ob ects Supported
Inacti e e t
P Access
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
LOCAL
LOCAL
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
W
W
R
B
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000

Table of Contents