Motor Unin - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A 1

Motor unin

Enter data into the following parameters to tune the motor and drive for optimal performance.
1 Induction Motor Auto unin
No
(Addr
Name
e )
T1-01
Auto-Tuning Mode
(701)
Selection
<1>
T1-02
Motor Rated Power
(702)
T1-03
Motor Rated Voltage
(703)
T1-04
Motor Rated Current
(704)
T1-05
Motor Base Frequency
(705)
T1-06
Number of Motor Poles Number of Poles
(706)
T1-07
Motor Base Speed
(707)
T1-11
Motor Iron Loss
(70B)
T1-12
T1 Tuning Start
(FFF0)
<1> The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<4> Default setting value differs depending on the motor code value and motor parameter settings.
2 PM Motor Auto unin
No
(Addr
Name
e )
T2-01
PM Motor Auto-Tuning
(750)
Mode Selection
T2-03
PM Motor Type
(752)
LCD Display
Tuning Mode Sel
2: Stationary Auto-Tuning for Line-to-Line Resistance
2: Term Resistance
3: Rotational Auto-Tuning for V/f Control Energy Saving
3: On-
DelayCompTune
Sets the motor rated power as specified on the motor nameplate.
Mtr Rated Power
Note:
Sets the motor rated voltage as specified on the motor nameplate. Default: 200.0
Rated Voltage
Sets the motor rated current as specified on the motor nameplate. Default:
Rated Current
Sets the rated frequency of the motor as specified on the motor
nameplate.
Rated Frequency
Sets the number of motor poles as specified on the motor
nameplate.
Sets the rated speed of the motor as specified on the motor
nameplate.
Rated Speed
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is
Mtr Iron Loss(W)
cycled. If T1-02 is changed, a default value appropriate for the
motor capacity that was entered will appear.
The drive starts tuning.
Tuning Ready
LCD Display
PM Tuning Mode
OL /PM
OL /PM
0: Standard Tuning
0: PM Motor Parameter Settings
PM Motor Type
OL /PM
OL /PM
0: IPM motor
0: IPM motor
1: SPM motor
1: SPM motor
Description
Use the following formula to convert horsepower
into kilowatts: 1HP = 0.746 kW.
Description
A 1
Motor unin
alues
Pa e
Default: 2
156
Range: 2, 3
Default:
<2>
Min.: 0.00 kW
156
Max.: 650.00
kW
V
<3>
156
Min: 0.0
Max: 255.0
<3>
<2>
Min.: 10% of
drive rated
current
156
Max.: 200% of
drive rated
current
Default: 60.0
Hz
156
Min.: 0.0
Max.: 240.0
Default: 4
Min.: 2
156
Max.: 48
Default: 1750 r/
min
156
Min.: 0
Max.: 14400
Default: 14 W
<4>
157
Min.: 0
Max.: 65535
No setting
157
available
alues
Pa e
Default: 0
157
Range: 0
Default: 1
157
Range: 0, 1
2 1
A