YASKAWA CIMR-ZU A Series Programming Manual page 290

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

B
BACnet Setup Parameters
Settin
MEMOBUS/Modbus
Settin 1 N2 (Metasys)
Settin 2 P1 (APOGEE FLN)
Settin
BACnet
Communications Fault Detection ime
Sets the time the communications must be lost before the drive triggers a CE fault.
No
H5-09
1
Unit Selection or MEMOBUS/Modbus e ister
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
No
H5-10
Unit Selection for MEMOBUS/Modbus Register 0025H
Settin
1
units
Settin 1 1
units
11 Communications Enter Function Selection
Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications.
to Enter Command on page
No
H5-11
Settin
Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Settin 1 Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
12
un Command Met od Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No
H5-12
Settin
F D/Stop
E /Stop
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will
start and stop the drive in reverse.
Settin 1
un/Stop F D/ E
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.
2
Name
Communications Fault Detection Time
Name
300.
Name
Communications Enter Function Selection
Name
Run Command Method Selection
Settin
an e
0.0 to 10.0 s
2
Settin
an e
0 or 1
Settin
an e
0 or 1
Settin
an e
0 or 1
De ault
2.0 s
De ault
0
Refer
De ault
0
De ault
0