1 2 b Application
b1
e erse Operation Selection
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No
b1-04
Settin
e erse Enabled
Possible to operate the motor in both forward and reverse directions.
Settin 1
e erse Disabled
Drive disregards a Reverse run command or a negative frequency reference.
b1 8
un Command Selection in Pro rammin Mode
As a safety precaution, the drive will not normally respond to a Run command input when the HOA keypad is being used to
adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode). If
required by the application, set b1-08 to allow the drive to run while in Programming Mode.
No
b1-08
Run Command Selection in Programming Mode
Settin
un Command Is Not Accepted in Pro rammin Mode
A Run command is not accepted while the HOA keypad is in Programming Mode.
Settin 1
un Command Is Accepted in Pro rammin Mode
A Run command is accepted in any HOA keypad mode.
Settin 2 Pro ibit Enterin Pro rammin Mode durin
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
b1 11 Dri e Delay ime Settin
If a time is set to b1-11, the drive will delay executing a Run command until the set time has expired. During Drive Delay
Time execution, the HOA keypad will display "WrUn". Both Alarm and Run indicators will blink while the drive waits to
execute the Run command.
No
b1-11
b1 1
P ase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No
b1-14
28
Run wait time t
Active deceleration time
Momentary Power Loss
Minimum Baseblock
Time (L2-03)
Min output
frequency
Fi ure 1 7
un
ait ime Dependin on Output Fre uency
Parameter Name
Reverse Operation Selection
Parameter Name
Parameter Name
Drive Delay Time Setting
Parameter Name
Phase Order Selection
Output frequency
(Max output
when Stop command
frequency)
was entered
Settin
Settin
un
Settin
Settin
100%
an e
De ault
0, 1
an e
De ault
0 to 2
an e
De ault
0 to 600 s
an e
De ault
0, 1
1
0
0
0