S3: Secondary Pi (Pi2) Control - YASKAWA CIMR-ZU A Series Programming Manual

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

No
(Addr
Name
e )
S2-15
Sequence Timer 3
(3214)
Reference Source
S2-16
Sequence Timer 4 Start
(3215)
Time
S2-17
Sequence Timer 4 Stop
(3216)
Time
S2-18
Sequence Timer 4 Day
(3217)
Selection
S2-19
Sequence Timer 4
(3218)
Selection
S2-20
Sequence Timer 4
(3219)
Reference Source
S
Secondary PI (PI2) Control
No
(Addr
Name
e )
S3-01
(321A) Secondary PI Enable
Selection
S3-02
(321B) Secondary PI User
Display
S3-03
(321C) Secondary PI Display
Digits
LCD Display
Selects the frequency reference source used for running the drive
when sequence timer 3 is active (only applicable when S2-14 is
set to 1 or 2).
Tmr 3 Ref Source
0: Operator (d1-01)
0: Operator (d1-01)
1: Operator (d1-02)
1: Operator (d1-02)
2: Operator (d1-03)
2: Operator (d1-03)
3: Operator (d1-04)
3: Operator (d1-04)
4: Terminals
4: Terminals
5: Serial communication
5: Serial com
6: Option card
6: Option PCB
Note:
Sets the start time for timer 4. The value must be set less than or
Tmr 4 Start Time
equal to S2-17.
Sets the stop time for timer 4. The value must be set greater than
Tmr 4 Stop Time
or equal to S2-16.
Tmr 4 Day Sel
Sets the days for which sequence timer 4 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Tmr 4 Seq Sel
Sets the action that occurs when sequence timer 4 is active.
0: Digital out only
0: Digital output only
1: Run
1: Run
2: Run - PI Disable
2: Run - PI disable
Selects the frequency reference source used for running the drive
when sequence timer 4 is active (only applicable when S2-19 is
set to 1 or 2).
Tmr 4 Ref Source
0: Operator (d1-01)
0: Operator (d1-01)
1: Operator (d1-02)
1: Operator (d1-02)
2: Operator (d1-03)
2: Operator (d1-03)
3: Operator (d1-04)
3: Operator (d1-04)
4: Terminals
4: Terminals
5: Serial communication
5: Serial com
6: Option card
6: Option PCB
Note:
LCD Display
PI2 Enable Sel
0: Secondary PI disabled
0: Disabled
1: Always
1: Always
2: Drive running
2: Drive running
3: Motor running
3: Motor running
Sets the scale value of 100% PI input.
PI2 UsrDspMaxVal
PI2 UsrDspDigits
0: No decimal places
0: No Dec (XXXXX)
1: One decimal place
1: 1 Dec (XXXX.X)
2: Two decimal places
2. 2 Dec (XXX.XX)
3: Three decimal places
3: 3 Dec (XX.XXX)
Description
H1-
= 12/13 overrides this sequence run timer
in drive software versions PRG: 1018 and later.
H1-
= 12/13 overrides this sequence run timer
in drive software versions PRG: 1018 and later.
Description
A 1 S Special Application
alues
Pa e
Default: 0
Range: 0 to 6
Default: 00:00
Min.: 00:00
Max.: 24:00
Default: 00:00
Min.: 00:00
Max.: 24:00
Default: 0
Range: 0 to 10
Default: 0
Range: 0 to 2
Default: 0
Range: 0 to 6
alues
Pa e
Default: 0
Range: 0 to 3
Default: 10000
Min.: 0
Max.: 60000
Default: 2
Range: 0 to 3
141
140
140
141
141
141
142
A
142
143
2 7