YASKAWA CIMR-ZU A Series Programming Manual page 143

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

S
Secondary PI Display Di its
Sets the decimal place display for secondary PI units.
No
S3-03
Settin
No Decimal Places
Settin 1 One Decimal Place
Settin 2
o Decimal Places
Settin
ree Decimal Places
S
Secondary PI Unit Selection
Sets units for secondary PI control function.
No
S3-04
Settin
Inc o
ater ( C)
Settin 1 Pounds per S uare Inc (PSI)
Settin 2 Gallons per Minute (GPM)
Settin
De rees Fa ren eit (F)
Settin
Cubic Feet per Minute (CFM)
Settin
Cubic Meters per our (CM )
Settin
Liters per our (LP )
Settin 7 Liters per Second (LPS)
Settin 8 Bar (Bar)
Settin
Pascals (Pa)
Settin 1
De rees Celsius (C)
Settin 11 Meters (Mtr) (Ft Feet)
Settin 12 Liters per Minute (LPM)
Settin 1
Cubic Meters per Minute (CMM)
Settin 1
No Unit
Settin 1
Percenta e ( )
S
Secondary PI Setpoint alue
Sets the secondary PI controller target value
No
S3-05
<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.
S
Secondary PI Proportional Gain Settin
Sets the proportional gain of the secondary PI controller. A setting of 0.00 disables P control.
No
S3-06
S
7 Secondary PI Inte ral ime Settin
Sets the integral time for the secondary PI controller. A setting of 0.0s disables integral control.
No
S3-07
Name
Secondary PI Display Digits
Name
Secondary PI Unit Selection
Name
Secondary PI Setpoint Value
Name
Secondary PI Proportional Gain Setting
Name
Secondary PI Integral Time Setting
1 11 S Special Parameters
Settin
an e
0 to 3
Settin
an e
0 to 15
Settin
an e
0.00 to 600.00
<1>
Settin
an e
0.00 to 25.00
Settin
an e
0.0 to 360.0 s
De ault
2
De ault
15
De ault
0.00
<2>
1
De ault
1.00
De ault
1.0 s
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000