YASKAWA CIMR-ZU A Series Programming Manual page 229

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

No
(Addr
Name
e )
E5-05
(32D)
Motor Stator Resistance PM Mtr Arm Ohms
<1>
E5-06
Motor d-Axis
(32E)
Inductance
<1>
E5-07
Motor q-Axis
(32F)
Inductance
<1>
E5-09
Motor Induction Voltage
(331)
Constant 1
<1>
E5-24
Motor Induction Voltage
(353)
Constant 2
<1>
<1> Selections may vary depending on the setting entered to o2-04.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the drive is set for
a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable motor capacity is
higher than 11 kW.
LCD Display
OL /PM
OL /PM
Set the resistance for each motor phase.
OL /PM
OL /PM
PM Mtr d Induct
Sets the d-Axis inductance for the PM motor.
OL /PM
OL /PM
PM Mtr q Induct
Sets the q-Axis inductance for the PM motor.
OL /PM
OL /PM
Sets the induced peak voltage per phase in units of
0.1 mV/(rad/s) [electrical angle]. Set this parameter when using
PM Mtr Ind V 1
an IPM motor with variable torque.
Set E5-24 to 0 when setting this parameter.
OL /PM
OL /PM
Sets the induced phase-to-phase rms voltage in units of
0.1 mV/(r/min) [mechanical angle].
PM Mtr Ind V 2
A 7 E Motor Parameters
Description
alues
Pa e
Default:
<2>
Min.: 0.000 Ω
70
Max.: 65.000 Ω
Default:
<2>
Min.: 0.00 mH
71
Max.: 300.00 mH
Default:
<2>
Min.: 0.00 mH
71
Max.: 600.00 mH
Default:
<2>
Min.: 0.0 mV/
(rad/s)
71
Max.: 2000.0
mV/
(rad/s)
Default:
<2>
Min.: 0.0 mV/
(r/min)
71
Max.: 6500.0
mV/
(r/min)
A
22