YASKAWA CIMR-ZU A Series Programming Manual page 269

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

No
(Addr
Name
e )
U5-06
(07D3) PI Adjusted Feedback
U5-07
AUTO Mode Frequency
(0072)
Reference Value
U5-08
HAND Mode Frequency
(0073)
Reference Value
U5-14
PI Output Upper 4 Digits PI Output U4
(086B)
U5-15
PI Output Lower 4 Digits PI Output L4
(086C)
U5-17
PI2 Setpoint
(086E)
U5-18
PI2 Feedback
(086F)
U5-19
PI2 Input
(0870)
U5-20
PI2 Output
(0871)
U5-30
Time Hr Min HHMM
(3000)
U5-31
Date Year
(3001)
U5-32
Date Mo Day MMDD
(3002)
U5-33
Day of the Week
(3003)
<1> Units determined by parameter b5-20, PI Setpoint Scaling.
<2> Analog Output selection text is: "PI Output 2".
U
Operation Status Monitors
No
(Addr
Name
e )
U6-01
Motor Secondary
(51)
Current (Iq)
U6-02
Motor Excitation
(52)
Current (Id)
U6-05
Output Voltage
(59)
Reference (Vq)
U6-06
Output Voltage
(5A)
Reference (Vd)
U6-21
Offset Frequency
(7D5)
LCD Display
Displays the difference of both feedback values if Differential
Feedback is used (U5-01 - U5-05).
If PI Square Root Feedback or Differential Feedback are enabled,
PI Diff Fdbk
U5-01 ≠ U5-06.
If PI Square Root Feedback or Differential Feedback are NOT
enabled, U5-01 = U5-06.
Displays the Frequency reference value at AUTO Mode.
AUTO mode Fref
Displays the Frequency reference value at HAND Mode.
HAND mode Fref
Displays Custom PI output. U5-14 shows the upper 4 digits.
Displays Custom PI output. U5-15 shows the lower 4 digits.
Displays the secondary PI setpoint.
PI2 Set-point
Displays the secondary PI feedback value.
PI2 Feedback
Displays the secondary PI input (deviation between PI target and
PI2 Input
feedback).
Displays the secondary PI control output.
PI2 Output
Displays the current time (Hours and Minutes).
Time Hr Min HHMM
Displays the current year.
Date Year
Displays the current date (Month and Day).
Date Mo Day MMDD
Date Week
Displays the current day of the week.
0: Sun
0: Sunday
1: Mon
1: Monday
2: Tues
2: Tuesday
3: Wed
3: Wednesday
4: Thur
4: Thursday
5: Fri
5: Friday
6: Sat
6: Saturday
LCD Display
Displays the value of the motor secondary current (Iq). Motor
Mot SEC Current
rated secondary current is 100%.
OL /PM
OL /PM
Mot EXC Current
Displays the value calculated for the motor excitation current (Id).
Motor rated secondary current is 100%.
OL /PM
OL /PM
Voltage Ref (Vq)
Output voltage reference (Vq) for the q-Axis.
OL /PM
OL /PM
Voltage Ref (Vd)
Output voltage reference (Vd) for the d-Axis.
Displays the frequency added to the main frequency reference.
Offset Frequency
Description
Description
A 1 U Monitors
Analo
Unit
Output Le el
10 V: 100%
0.01%
No signal output
0.01 Hz
available
No signal output
0.01 Hz
available
10V: (b5-43 x
10000) + b5-44
1
<2>
No signal output
0.01
available
10 V: Max
0.01%
frequency
10 V: Max
0.01%
frequency
10 V: Max
0.01%
frequency
10 V: Max
0.01%
frequency
No signal output
1
available
No signal output
1
available
No signal output
1
available
No signal output
1
available
Analo
Unit
Output Le el
10 V: Motor
secondary rated
0.1%
current
10 V: Motor
secondary rated
0.1%
current
10 V: 200 Vrms
A
0.1 Vac
<1>
10 V: 200 Vrms
0.1 Vac
<1>
0.1%
2