YASKAWA CIMR-ZU A Series Programming Manual page 246

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A 1 L Protection Function
No
(Addr
Name
e )
L3-26
Additional DC Bus
(455)
Capacitors
L3-27
Stall Prevention
(456)
Detection Time
<1> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.
<2> The setting range is 0 to 2 in OLV/PM control mode.
<3> Default setting is dependent on parameter E1-01, Input voltage Setting.
<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<5> Default setting is determined by parameter A1-02, Control Mode Setting.
<6> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<7> Default setting is dependent on parameter o2-04, Drive Model Selection.
L
Speed Detection
No
(Addr
Name
e )
L4-01
Speed Agreement
(499)
Detection Level
L4-02
Speed Agreement
(49A)
Detection Width
L4-03
Speed Agreement
(49B)
Detection Level (+/-)
Speed Agreement
L4-04
Detection Width
(49C)
(+/-)
Frequency Reference
L4-05
Loss Detection
(49D)
Selection
L4-06
Frequency Reference
(4C2)
at Reference Loss
L4-07
Speed Agreement
(470)
Detection Selection
L
Fault estart
No
(Addr
Name
e )
L5-01
Number of Auto Restart
(49E)
Attempts
Auto Restart Fault
L5-02
Output Operation
(49F)
Selection
L5-03
Time to Continue
(4A0)
Making Fault Restarts
L5-04
Fault Reset Interval
(46C)
Time
2
LCD Display
When DC bus capacitors have been added externally, be sure
ExtDC busCapSize
to add those values to the internal capacitor table for proper DC
bus calculations.
Sets the time the current must exceed the Stall Prevention level
Stl Prev DetTime
to activate Stall Prevention.
LCD Display
L4-01 sets the frequency detection level for digital output
Spd Agree Level
functions H2-
L4-02 sets the hysteresis or allowable margin for speed
Spd Agree Width
detection.
L4-03 sets the frequency detection level for digital output
Spd Agree Lvl+-
functions H2-
L4-04 sets the hysteresis or allowable margin for speed
Spd Agree Wdth+-
detection.
Ref Loss Sel
0: Stop. Drive stops when the frequency reference is lost.
0: Stop
1: Run. Drive runs at a reduced speed when the frequency
1: Run@L4-06PrevRef
reference is lost.
Sets the percentage of the frequency reference that the drive
Fref at Floss
should run with when the frequency reference is lost.
Freq Detect Sel
0: No detection during baseblock.
0: No Detection @BB
1: Detection always enabled.
1: Always Detected
LCD Display
Sets the number of times the drive may attempt to restart after
Num of Restarts
the following faults occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,
STo, Uv1.
Restart Sel
0: Fault output not active.
0: Flt Outp Disabld
1: Fault output active during restart attempt.
1: Flt Outp Enabled
Enabled only when L5-05 is set to 0. Causes a fault if a fault
Max Restart Time
restart cannot occur after the set time passes.
Sets the amount of time to wait between performing fault
Flt Reset Wait T
restarts.
Description
Description
= 2, 3, 4, 5.
= 13, 14, 15, 16.
Description
alues
Pa e
Default: 0 μF
Min: 0
112
Max: 65000
Default: 50 ms
Min.: 0
112
Max.: 5000
alues
Pa e
Default: 0.0 Hz
Min.: 0.0
112
Max.: 240.0
Default: 2.0 Hz
Min.: 0.0
112
Max.: 20.0
Default: 0.0 Hz
Min.: -240.0
112
Max.: 240.0
Default: 2.0 kHz
Min.: 0.0
112
Max.: 20.0
Default: 1
113
Range: 0, 1
Default: 80.0%
Min.: 0.0
113
Max.: 100.0
Default: 0
113
Range: 0, 1
alues
Pa e
Default: 0
Min.: 0
114
Max.: 10
Default: 0
114
Range: 0, 1
Default: 180.0 s
Min.: 0.0
114
Max.: 600.0
Default: 10.0 s
Min.: 0.5
116
Max.: 600.0