YASKAWA CIMR-ZU A Series Programming Manual page 135

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

o
2 Copy Allo ed Selection
Allows and restricts the use of the Copy function.
No
o3-02
Settin
Disabled
Settin 1 Enabled
o
Maintenance Monitor Settin s
o
1 Cumulati e Operation ime Settin
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
Note:
be displayed in monitor U4-01.
No
o4-01
o
2 Cumulati e Operation ime Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.
No
o4-02
Settin
Po er on ime
The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Settin 1
un ime
The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)
and when there is voltage output.
o
Coolin Fan Operation ime Settin
Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. "300"
Note:
will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No
o4-03
o
Capacitor Maintenance Settin
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the DC bus capacitors.
The actual maintenance time will depend on the environment where the drive is used.
Note:
No
o4-05
o
7 DC Bus Pre C ar e elay Maintenance Settin
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
The actual maintenance time will depend on the environment where the drive is used.
Note:
No
o4-07
DC Bus Pre-charge Relay Maintenance Setting
Name
Copy Allowed Selection
Name
Cumulative Operation Time Setting
Name
Cumulative Operation Time Selection
Name
Cooling Fan Operation Time Setting
Name
Capacitor Maintenance Setting
Name
1 1 o Operator
elated Settin s
Settin
an e
0, 1
Settin
an e
0 to 9999 h
Settin
an e
0, 1
Settin
an e
0 to 9999 h
Settin
an e
0 to 150%
Settin
an e
0 to 150%
De ault
0
De ault
0 h
De ault
1
De ault
0 h
1
De ault
0%
De ault
0%
1