Alarm Outputs or Maintenance Monitors
An output can be set up to inform the user when a specific components has neared its expected performance life.
When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2-
terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected performance
life, or when the IGBTs have reached 50% of their expected performance life. Additionally the HOA keypad will display an
alarm like shown in
Table 2.5
OA eypad Alarm Display
LT-1
<1>
LT-2
<1>
LT-3
<1>
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2-
will also trigger a digital output that is programmed for alarm indication (H2-
<2> This alarm message will always be output, even if the Maintenance Monitor function is not assigned to any of the digital outputs (H2-
The alarm will also trigger a digital output that is programmed for alarm indication (H2-
elated Dri e Parameters
Use parameters o4-03, o4-05, o4-07, and o4-09 to reset a Maintenance Monitor to zero after replacing a specific component.
Refer to Parameter List on page 211
NO ICE If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will continue
to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset, the drive will
not have the correct value of the performance life for the new component.
to indicate the specific components that may need maintenance.
able 2
The cooling fans have reached 90% of their designated
life time.
The DC bus capacitors have reached 90% of their
designated life time.
The DC bus charge circuit has reached 90% of its
designated life time.
for details on parameter settings.
Maintenance Alarms
Function
= 10).
= 10).
2
Periodic Maintenance
Correcti e Action
Replace the cooling fan.
Contact a Yaskawa representative or the
nearest Yaskawa sales office on
possible drive replacement.
Contact a Yaskawa representative or the
nearest Yaskawa sales office on
possible drive replacement.
= 2F). The alarm
= 2F), the
= 2F).
2
1