YASKAWA CIMR-ZU A Series Programming Manual page 262

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

A 1
Motor unin
No
(Addr
Name
e )
T2-04
PM Motor Rated Power Mtr Rated Power
(730)
T2-05
PM Motor Rated
(732)
Voltage
T2-06
PM Motor Rated Current Rated Current
(733)
T2-07
PM Motor Base
(753)
Frequency
T2-08
Number of PM Motor
(734)
Poles
T2-10
PM Motor Stator
(754)
Resistance
T2-11
PM Motor d-Axis
(735)
Inductance
T2-12
PM Motor q-Axis
(736)
Inductance
T2-13
Induced Voltage
(755)
Constant Unit Selection
T2-14
PM Motor Induced
(737)
Voltage Constant
T2-15
Pull-In Current Level for
(756)
PM Motor Tuning
T2-18
T2 Tuning Start
(FFF1)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<3> Default setting is dependent on parameter T2-02, PM Motor Code Selection, and the drive capacity.
2 2
LCD Display
OL /PM
OL /PM
Sets the motor rated power.
Note:
OL /PM
OL /PM
Enter the motor rated voltage as indicated on the motor nameplate.
Rated Voltage
OL /PM
OL /PM
Enter the motor rated current as indicated on the motor nameplate.
OL /PM
OL /PM
Enter the motor base frequency as indicated on the motor
Base Frequency
nameplate.
OL /PM
OL /PM
Enter the number of motor poles for the PM motor as indicated
on the motor nameplate.
OL /PM
OL /PM
Arm Resistance
Enter the rotor resistance for the PM motor as indicated on the
motor nameplate.
OL /PM
OL /PM
Enter the d-axis inductance for the PM motor as indicated on the
d-Axis Induct
motor nameplate.
OL /PM
OL /PM
Enter the q-axis inductance for the PM motor as indicated on the
q-Axis Induct
motor nameplate.
OL /PM
OL /PM
Iduct Volt Unit
0: mV/(r/min). E5-09 will automatically be set to 0.0, and E5-24
0: mV/RPM
will be used.
1: mV/(rad/sec)
1: mV/(rad/sec). E5-24 will automatically be set to 0.0, and E5-09
will be used.
OL /PM
OL /PM
Enter the induced voltage coefficient for the PM motor as
Induct Volt Coef
indicated on the motor nameplate. Setting units are determined
by parameter T2-13, Induced Voltage Constant Unit Selection.
OL /PM
OL /PM
Sets the amount of pull-in current to use for Auto-Tuning as a
Pull-In I Lvl
percentage of the motor rated current. Increase this setting for
high inertia loads.
OL /PM
OL /PM
T2 Tuning Start
The drive starts tuning.
Description
Use the following formula to convert horsepower
into kilowatts: 1 HP = 0.746 kW.
alues
Pa e
Default:
<1>
Min.: 0.00 kW
157
Max.: 650.00
kW
Default: 200.0
V
<2>
157
Min.: 0.0
Max.: 255.0
<2>
Default:
<1>
Min.: 10% of
drive rated
current
158
Max.: 200% of
drive rated
current
Default: 87.5
Hz
158
Min.: 0.0
Max.: 240.0
Default: 6
Min.: 2
158
Max.: 48
Default:
<3>
Min.: 0.000 Ω
158
Max.: 65.000 Ω
Default:
<3>
Min.: 0.00 mH
158
Max.: 600.00
mH
Default:
<3>
Min.: 0.00 mH
158
Max.: 600.00
mH
Default: 0
158
Range: 0, 1
Default:
<3>
Min.: 0.1
158
Max.: 2000.0
Default: 30%
Min.: 0
159
Max.: 120
No setting
159
available