YASKAWA CIMR-ZU A Series Programming Manual page 235

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1
Function
Settin
31
PI integral hold
34
PI soft starter cancel
35
PI input level selection
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
50
Motor Pre-Heat 2
51
Sequence Timer Disable SeqTimer Disable
52
Sequence Timer Cancel
60
Motor pre-heat 1
External Speed Search
61
command 1
External Speed Search
62
command 2
63
Field weakening
65
KEB Ride-Thru 1 (N.C.) KEB Ridethru NC
66
KEB Ride-Thru 1 (N.O.) KEB Ridethru NO
Communications test
67
mode
68
High slip braking
69
Jog 2
6A
Drive enable
6D
AUTO mode select
1 Multi Function Di ital Input Selections
LCD Display
Open: Performs integral operation.
PI Intgrl Hold
Closed: Maintains the current PI control integral value.
Open: PI soft starter is enabled.
PI SFS Cancel
Closed: Disables the PI soft starter b5-17.
PI Input Invert
Closed: Inverts the PI input signal.
Open: Stop
Closed: Forward run
FwdRun 2Wire Seq
Note:
Open: Stop
Closed: Reverse run
RevRun 2WireSeq
Note:
Open: Stop
Closed: Run
Run/Stp 2WireSeq
Note:
Open: Forward
Closed: Reverse
FWD/REV 2WireSeq
Note:
Offset Freq 1
Closed: Adds d7-01 to the frequency reference.
Offset Freq 2
Closed: Adds d7-02 to the frequency reference.
Offset Freq 3
Closed: Adds d7-03 to the frequency reference.
Motor Preheat 2
Closed: Triggers Motor Pre-Heat 2.
Closed: Drive ignores sequence timers and runs normally.
SeqTimer Cancel
Closed: Sequence Timer Cancel .
Motor Preheat 1
Closed: Triggers Motor pre-heat 1.
Closed: Activates Current Detection Speed Search from the maximum output
Speed Search 1
frequency (E1-04).
Speed Search 2
Closed: Activates Current Detection Speed Search from the frequency reference.
Field Weak
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
Open: KEB Ride-Thru 1 enabled.
Closed: KEB Ride-Thru 1 enabled.
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays "PASS" if the
Comm Test Mode
test completes successfully.
HighSlipBraking
Closed: Activates High Slip Braking to stop the drive during a Run command.
Cause the drive to ramp to the jog frequency (d1-17).
Jog 2
Note:
Open: Drive disabled. If this input is opened during run, the drive will stop as
specified by b1-03.
Closed: Ready for operation.
Drive Enable
Note:
Legacy Operation Mode (S5-04 = 0)
• Open: HAND reference is selected (based on S5-01)
• Closed: AUTO reference is selected (based on b1-01)
Normal Operation Mode (S5-04 ≠ 0)
AUTO Mode Sel
Note:
• Open: Drive is in OFF or HAND mode.
• Closed: Drive is in AUTO mode (when HAND mode select input is open)
A
Parameters Multi Function erminals
Description
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 40 or 41.
Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
This selection is only available in 3-wire control.
H1-
= 6A must be opened for Emergency Override (H1-
AF) to function.
The drive will always be in AUTO mode at power up when
S5-04 is set to 1.