YASKAWA CIMR-ZU A Series Programming Manual page 90

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

1 7
erminal Functions
Frequency reference
L4-03
0 Hz
Output frequency
User Set
Speed Agree 2
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 112
Settin 1
Fre uency Detection
The output opens when the output frequency or motor speed rises above the detection level set in L4-03 plus the detection
with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set in L4-03. The
detection level L4-03 is a signed value; detection works in the specified direction only.
Status
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
Frequency
detection 3
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 112
Settin 1
Fre uency Detection
The output closes when the output frequency or motor speed is above the detection level set in L4-03. The terminal remains
closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Status
Open
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Closed
Output frequency or motor speed exceeded L4-03.
The detection level L4-03 is a signed value; detection works in the specified direction only.
Note:
During
Forward
OFF
OFF
ON
Fi ure 1
User Set Speed A ree 2 E ample
Output Frequency
ON
OFF
Fi ure 1 7 Fre uency Detection
Frequency reference
L4-03
+
L4-04
Frequency reference – L4-04
L4-03 – L4-04
ON
it a Positi e L
Description
L4-04
L4-03
E ample
it a Positi e L
Description
+
L4-04
Output frequency
Frequency reference
alue
for more details.
alue
for more details.