1 8 L Protection Functions
2. When the Forward/Reverse command is removed, the drive can perform a self-diagnostic check and attempt to restart the fault
automatically.
A NING Sudden Movement Hazard. Do not use the fault restart function in lifting applications. Fault restart may cause the machine to
drop the load, which could result in death or serious injury.
The drive can attempt to restart itself following the faults listed below.
Fault
GF
LF
oC
oH1
oL1
oL2
oL3
<1> When L2-01 is set to 0 through 2 (continue operation during momentary power loss).
Use parameters L5-01 to L5-05 to set up automatic fault restart.
Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart.
L
1 Number o Auto estart Attempts
Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,
the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
No
L5-01
L
2 Auto estart Fault Output Operation Selection
Determines if a fault output is triggered (H2-
No
L5-02
11
Name
Ground Fault
Output Open Phase
Overcurrent
Drive Overheat
Motor Overload
Drive Overload
Overtorque 1
Name
Number of Auto Restart Attempts
= E) when the drive attempts to restart.
Name
Auto Restart Fault Output Operation Selection
Fault
oL4
ov
DC Bus Overvoltage
PF
Uv1
DC Bus Undervoltage
STo
Pull-Out Detection
Settin
0 to 10 Times
Settin
0, 1
Name
Overtorque 2
Input Phase Loss
<1>
an e
De ault
0 Times
an e
De ault
0