C 1 APOGEE FLN Set Up

C 1 APOGEE FLN Set Up
The APOGEE FLN (P1) communication protocol is applicable in Z1000 software versions PRG: 1015 and later.
A Yaskawa America, Inc. representative is responsible for proper configuration of the drive for its primary application, while
a Siemens Building Technologies, Inc. representative is responsible for field panel programming to make use of the drive
functionality in the building automation system. As such, there must be coordination between the Yaskawa America and
Siemens Building Technologies representatives to ensure that the programming of the drive is consistent with the particular
application requirements. After verifying that the drive installation and wiring are correct, apply power to the drive.
lists the parameters and values required for proper APOGEE FLN communication and control.
1
Z1000 parameter settings For APOGEE FLN communications
Parameter Number
b1-01
b1-02
H1-03
H5-01
H5-02
H5-08
NO ICE Damage to Equipment. A Yaskawa representative should set the drive parameters to their appropriate values. Changes made to
the settings of the parameters in
able C 1 Dri e APOGEE FLN Communication Parameter Settin s
OA eypad Display
Reference Source
Run Source
Digital Input Terminal S3 Function Selection
Serial Comm Adr
Serial Baud Rate
Protocol Select
Table C.1
can result in damage to the drive or building equipment.
APOGEE FLN Settin
2: Serial Com
2: Serial Com
70: Drive Enable2
Select the drive address (default = 1Fh (31 dec))
2: 4800 Baud
2: P1
Table C.