YASKAWA CIMR-ZU A Series Programming Manual page 133

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

o2
OA eypad Functions
These parameters determine the functions assigned to the operator keys.
o2 2 OFF ey Function Selection
Determines if the OFF key on the HOA keypad will stop drive operation when the drive is controlled from a remote source
(i.e., not from HOA keypad).
The keypad OFF key is not functional when the drive is in Emergency Override.
Note:
No
o2-02
Settin
Disabled
Settin 1 Enabled
The OFF key will terminate drive operation even if the Run command source is not assigned to the HOA keypad. Cycle the
Run command to restart the drive if the drive has been stopped by pressing the OFF key.
o2
User Parameter De ault alue
After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values.
No
o2-03
Settin
No C an e (A aitin Command)
Settin 1 Set User Initiali e alues
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Settin 2 Clear User Initiali e alues
All user-set defaults for "User Initialize" are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.
o2
Dri e Model Selection
Set this parameter when replacing the control board or the terminal board.
information on drive model selection.
NO ICE Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No
o2-04
Change o2-04 setting only when necessary.
Note:
o2
Fre uency e erence Settin Met od Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the HOA keypad while in Drive
Mode.
No
o2-05
Frequency Reference Setting Method Selection
Settin
EN E
ey e uired
The ENTER key must be pressed every time the frequency reference is changed using the HOA keypad for the drive to accept
the change.
Settin 1 EN E
ey not e uired
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the HOA keypad.
The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after remaining unchanged
for 5 seconds.
Name
OFF Key Function Selection
Refer to A1-03: Initialize Parameters on page 19
Name
User Parameter Default Value
Name
Drive Model Selection
Name
1 1 o Operator
Settin
an e
0, 1
for details on drive initialization.
Settin
an e
0 to 2
Refer to Defaults by Drive Model on page 274
Settin
an e
-
Settin
an e
0, 1
elated Settin s
De ault
1
De ault
0
for
De ault
Determined by
drive capacity
1
De ault
0
1