YASKAWA CIMR-ZU A Series Programming Manual page 195

For hvac fan and pump, 200/400 v class: 2.2 to 110/370 kw 3 to 150/500 hp
Table of Contents

Advertisement

Fi ure 2
8
Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.
Coolin Fan eplacement
A NING Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply can result in serious
personal injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait for at least
the time specified on the warning label, once all indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior to servicing.
CAU ION Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or moderate injury. Shut off the power
to the drive when replacing the cooling fan. To prevent burns, wait at least 15 minutes and ensure the heatsink has cooled down.
NO ICE Follow cooling fan and circulation fan replacement instructions. Improper fan replacement may cause damage to equipment. When
installing the replacement fan into the drive, make sure the fan is facing upwards. Replace all fans when performing maintenance to help
ensure maximum useful product life.
emo in and Disassemblin t e Coolin Fan Unit
1
Remove the covers. Refer to the User Manual packaged with the drive for details on removing the drive covers.
eattac t e Dri e Co er 2A 1
A
2
Fi ure 2 7
emo e t e Front Co er
to 2A 27
A 1
to A 2
A
2
A
2
2
Dri e Coolin Fans